K2200 Series | Installation Guide | 5.0 Installation Details EN | 38
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
Figure 24: Case Tamper Wiring
T+ T-
Tamper
Case Tamper Switch
N/C
Note:
This is a normally closed switch therefore you should
use a short piece of cable to link the two terminals
before powering up. If not, you will get an immediate
Case Tamper alarm.
5.5.3 Override Input
This is a normally open input that, when closed, will
cause all the locks on the controller to release. This
may be fitted to the output of a Manual Emergency
Override switch. All the doors on the door
controller will remain open until the switch opens
again.
Figure 25: Override Input Wiring
F+ F-
Emergency Override Switch
N/O
Note:
If it is connected on a master controller, the doors on the
master and those on any associated slaves will open and
remain open until the switch opens again provided the
master override input option has been programmed. For
details, refer to Readykey K2200 Series Controllers
User Guide (Bosch P/N: 47491, PAC P/N: 17376).
ANY FAILURE OF THE DOOR
CONTROLLER OR CABLING WILL
PREVENT THIS MEANS OF
RELEASING THE DOORS FROM
WORKING. THEREFORE THIS INPUT
MUST NOT BE CONSIDERED AS A
PRIMARY SAFETY MECHANISM – see
Section 5.4.6 Lock Output on page 36.