K2200 Series | Installation Guide | 5.0 Installation Details EN | 27
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
5.3.6 Battery Backup
The 12VDC 7AH battery (if in a fully-charged, good
condition) provides approximately 2.0 hours of
standby time for a fully loaded system.
A battery charging facility is available that can
provide up to 0.5 A at 13.8 VDC or 0.25 A at 27.6
VDC.
Door Controllers
The battery backup voltage must match
the lock output voltage, i.e. 12 V VDC or
24 V VDC. You may use two 12 VDC
batteries in series to provide 24 VDC.
The capacity of the battery required should be
calculated based on:
The current consumption of the door controller
(1 A).
The current consumption of the devices attached
to the reader channels (up to 800 mA).
The current consumption of the locks when
operating normally (up to 2 A each).
The type of lock, continuous (fail-safe) or
intermittent (fail-secure).
The length of time the system should operate
without mains power.
The following tables will help you estimate the
current.
Lock Supply Current
For continuous, or fail-safe locks the continuous lock
supply current is the current drawn by the lock. For
fail-secure locks, however, you need to estimate the
equivalent continuous current by using the following
equation:
Figure 14: Continuous Current Estimation
Equation
CLC = {Lock Current Rating x LRT} x
NOP / 3600
where
CLC = Equivalent Continuous Lock Current
LRT = Lock Release Time (in seconds)
NOP = Number of Operation per hour
The lock current rating should be indicated in the
lock specification.
Example:
A 500 mA lock strike with a 5 second lock release time,
operating 50 times an hour would give:
CLC = (500 x 5) x 50 / 3600 = 35 mA
Note:
If you have any doubt about the current drawn by a
lock, you should measure it at the controller using a
meter.
The maximum current that should be drawn from
each lock output is:
2.0 A at 12 VDC 1.0 A at 24 VDC
In Table 11 record the type and current consumption
of each lock fitted.
Table 11: Continuous Lock Supply Current
Channel Type:
Continuous/
Intermittent
Continuous
Lock Current
1
2
3
4
Total =
Reader Supply Current
There is a maximum of
200 mA available per reader channel on the 18 V
supply. Readykey readers of all types draw
approximately 90 mA each continuously. If you fit
Alarm Modules or AEMs, a reader combiner or
Wiegand interface unit, you should ensure that the
maximum current available, 800 mA, is not
exceeded.