D9412GV2/D7412GV2 | Operation and Installation Guide | 4.0 Installation
.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04 17
4.5.3 Enabling Ground Fault Detection
To enable the Ground Fault Detect Enable feature:
1. Lock (close) the S4 Ground Fault Detect Pin on
the control panel (Figure 4).
If your control panel has Version 7.02
firmware or earlier, you must do Step 2.
2. Program the Area 5 Silent Alarm Relay to a non-
zero value (1 to 128).
In remote programming software (RPS), the Area
5 Silent Alarm Relay is located in RELAY
PARAMETERS, Area Wide Relays, and Silent
Alarm Area 5 (Figure 5).
Figure 4: Ground Fault Detect (S4)
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
BATTERY POSITIVE ONLY
REL AY A
REL AY B
REL AY C
+ AUX POWER
CLASS 2 TRANSFORME R
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do not shor t
Requires Uns witc hed Outlet
Do not share with other equipmen t
GROUND FAULT DETECT
Enabled
Disab led
PHONE
LED
RED
ON when
communicating
OFF when idle
Commercial Protect ed-Premises Control Panel
D9412GV2 Control Panel is UL Listed For Central Station, Local, Auxiliary, Proprietary, and
Household Fire Alarm, and Central Station, Local, Police Station Connect, Household Burglar Alarm
and Encrypted Line Security when communicating via a network.
System is intended to be checked by a Qualified Technician at least every 3 years.
The types of initiat ing circuits the control panel has been approved for are A, M, W, SS.
The ty pe s of signaling the control panel has been approved f or are DAC, OT, NC
VOLTAGE RANGES
Open 3.7 - 5.0 VDC Short 0.0 - 1.3 VDC
Normal 2.0 - 3.0 VDC
Reset Pin
Disable all except Battery
Charging and Programming
PERIPHERAL DEVICE CONNECTIONS
RED POWER +
YELLOW DATA BUS A
GREEN DATA BUS B
BLACK C OMMON
ZONEX OUT 1
ZONEX IN 1
N.F.P.A.
Style 4.0
Signaling
Line
Circuits
F01U003643-01
1211 13
Point 1
Point 2
1514 16
Point 3
Point 4
1817 19
Point 5
Point 6
2120 22
Poin t 7
Poi nt 8
LEDs Off When Normal
Charging Status
Low Battery - 12.1 VDC
YEL
RED
10.2 VDC - Batter y Load Shed
This equipment sh ould be installed in accordance with the NFPA 70 (National Electrical Code)
and NFPA 72 (National Fire Alarm Code) for Local, Centr al Station, Proprietary and Household Fire
Warning Systems a nd under the limits of the Local Authority Hav ing Jurisdiction (National Fire
Protection Association, Battermarch Par k, Quincy, MA 02269). Printed informat io n describing
proper installation, operation, testing, maintenance, evacuation planning and repair service is to
be provided with t his equipment.
D9412GV2
26
25
ZONEX PO WER +
24
ZONEX COMMON
23
PHON E LINE SE IZED
TIP
RING
TEL CO C OR D
MODEL D161
SDI Connector
ZONEX OUT 2
ZONEX IN 2
Refer to the D9412GV2/D7412GV2 Approved Applications Compliance Guide (P/N: F01U003639)
For System Wiring Diagram, Issue A and for Compatible Smoke Detectors
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 1.4 Amps for the Control Panel and all
Accessory Devices. For System Loading, refer to the D9412GV2/D7412GV2
Operation and Installation G uide (P/N: F01U003641).
(P/N: F01U003641) for Power Requirements relating to Terminals 6 and 7 .
CAUTION:
Refer to the D9412GV2/D7412GV2 Operation and Installation Guide
All external connections except Terminal 5 (battery positive) are inherently power
limited. Requirements for battery standby time might reduce allowable output.
WARNING!
Multi-Battery installation requires
Model D122/D122L Dual Battery
Harness. Improper install ation can
be a fire hazard.
Battery: Replace every 3 to
5 years with one or two Model
D126 or D1218 12V Lead Acid
Batteries.
GRN
D5200/D5360
PROG CONN
Point 8
S3 Option
Closed = 1K
Ω
EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 K
Ω
Incorrect wiring will
damage t his equipment.
Suitable for dry indoor
use only.
Devices powered by the
AUX power output must
be supervised.
Minimum system require ments for Classif ica tion in accordance with ANSI/SIA CP-0 1-2000:
UL Listed and Classified control u nit Model D9412GV2, D7412GV2, or D7212GV2;
UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;
UL Listed Local Bell
CAUTION: Avoid damage to Panel.
Do not connect 24 V to terminals.
Maximum charging current 1.4 A
PROGRAMMABLE
ALARM OUTPUTS
Ter m i nal s
SWITCHED AUX
and
67
Termi nal
8
Reset Pin
Disable All Except Ba ttery
Charging And Programming
27
PROG
CONN
26
25
24
2
1
1 - Locked (Closed) 2 - Unlocked (Open)
Figure 5: Area 5 Silent Alarm Relay in RPS
4.5.4 D7212GV2 Ground Fault Specifications
Table 6 provides the impedance specifications for
detecting ground faults when any terminal or field
wiring is shorted to ground.
Table 6: Ground Fault Impedance
Specifications
Impedance Control Panel Detects Ground Fault
<300
Yes
300 to
200>k
Detection depends upon the terminal
> 200 k
No