History Buffer
The system stores events in a 99‑event history buffer.
Notice
The number of events that can be stored in the
history buffer increases to 499 with the addition
of a D7039 Multiplex Expansion Module.
Central Station Reporting
The FPD-7024 FACPs send reports to two telephone
numbers (or, if a Conettix interface module is
installed, IP addresses) to an appropriate Conettix
receiver at the central station with full single, double,
and backup reporting. The panel supports
communication in BFSK, SIA, Contact ID, Modem IIIa
2
,
and 4/2 or 3/1 Tone Bursts.
Dirty Smoke Detector Monitoring
All on‑board zones and FPC‑7034 zones are
continuously monitored for smoke detectors signaling
a dirty condition using the Bosch Chamber Check
feature and CleanMe protocol. If a detector's smoke
chamber is dirty, the detector sends a CleanMe signal
on the two‑wire loop or a dirty detector signal on the
addressable loop. The control panel annunciates that
there is a dirty detector on the loop or the address.
The Chamber Check feature signals a dirty smoke
chamber using the LED on the detector head.
Accessories
The FPD‑7024 enclosure has space for additional
accessory modules and two D1218 (18 Ah) batteries
or two D126 (7 Ah) batteries.
Certifications and approvals
Region Certification
USA UL UOJZ: Control Units, System (ANSI/UL
864)
FM FPD-7024
CSFM see our website
FCC ESVAL04B7024
FDNY-
CoA
#6173
Installation/configuration notes
Compatible Products
The following products are compatible (refer to the
product datasheet for country‑specific certifications/
approvals) with the FPD‑7024 FACP:
Category Product ID and Description
Batteries and
Power Supplies
D126 12 V, 7 Ah battery
D1218 12 V, 18 Ah battery
FPP‑RNAC‑8A‑4C Remote NAC power supply
Detectors For two‑wire detector compatibility, refer to
FPD‑7024 Smoke Detector Compatibility List
Technogram (P/N: F01U010790)
Keypads and
Annunciators
D7030X Eight‑point LED annunciator (eight red)
D7030X‑S2 Eight‑point LED annunciator
(two yellow, six red)
D7030X‑S8 Eight‑point LED annunciator
(eight yellow)
D7032 Eight‑point LED annunciator expander
(eight red)
FMR‑7033 LCD fire system keypad
FMR‑7036 LCD annunciator
Modules D132B Smoke detector reversing relay module
D184A Local energy kit
D185 Reversing polarity module
D275 EOL power supervision module
FPC‑7034 Four‑point expander
D7039 Multiplex expansion module
Option Bus
Devices
D7035 Octal relay module
D7035B Octal relay module in box
DX4010V2 USB/serial interface module
DX4020 Network interface module
B420 Ethernet communicator
B426 Ethernet communication module
B440 Conettix plug‑in cellular
B441 Conettix plug‑in cellular
B442 Conettix plug‑in GPRS cellular
B443 Conettix plug‑in HSPA+ cellular
B450 Conettix plug‑in communicator interface
ITS-DX4020-G GPRS/GSM communicator
NAC Devices Refer to FPD‑7024 Device Compatibility List
Technogram (P/N: F01U010791)
The following additional products are compatible with
the FPD‑7024 Addressable FACPs:
Category Product ID and Description
Detector Heads
and Bases
D7050 Addressable Photoelectric Smoke Detector
Head
D7050TH Addressable Photoelectric Smoke and
Heat Detector Head
D7050‑B6 Detector Base
Modules D7042 Multiplex eight‑input remote module
2 | FPD‑7024 Fire Alarm Control Panels