4.8.4 DX2010 Configuration
DX2010 Configuration Options
Address:
1257 = DX2010 Address 101
1258 = DX2010 Address 102
1259 = DX2010 Address 103
1260 = DX2010 Address 104 (DS7240V2 only)
1261 = DX2010 Address 105 (DS7240V2 only)
Default: 0
Selections: 0 to 11
Enter This Data Digit to Select Options
DX2010 Configuration Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
300 ms Debounce Time
150 ms Debounce Time
75 ms Debounce Time
30 ms Debounce Time
Tamper-wired EOL Resistors
Single 2.2 k EOL Resistor
• • • •
Single 2.2 k EOL Resistor, 30% Zone
Reserved
When the location’s device parameter is set to 2 (see Location ##, Device on page 83), the sensor loop is taken from
a DX2010 module. This parameter configures the input modules. The debounce time selects how quickly the
input reacts to a change.
The single 2.2 k EOL resistor configurations use only one EOL resistor. The tamper-wired EOL resistor
configuration uses two-2.2 k EOL resistors and can report tamper as well as alarm.
The 30% zone causes an alarm whenever the EOL resistance changes by more than 30%. This setting makes the
zone more sensitive to false alarms than a standard zone. The 30% zone should only be used if required by local
regulations.