D296/D297 | Installation Instructions | 11.0 Specifications
11.0 Specifications
Table 7: Specifications
Operating Voltage
D296: 18.0 VDC to 32.0 VDC
D297: 10.2 VDC to 15.0 VDC
Standby Current
D296 Receiver: 45 mA at 24 VDC
D296 Transmitter: 20 mA at 24 VDC
D297 Receiver: 50 mA at 12 VDC
D297 Transmitter: 20 mA at 12 VDC
Receiver Alarm
Current
D296: 70 mA maximum
D297: 75 mA at 12 VDC
Range (the distance
between the
transmitter and
receiver)
30 ft to 350 ft (9 m to 107 m)
Spacing (the distance
between the systems)
Allow no more than 60 ft (18 m) between systems. Spacing of 60 ft (18 m) is confirmed by
Underwriters Laboratories, Inc. (UL) testing.
Pointability
Internally pointable optics for ±90° horizontal, and ±10° vertical adjustment.
Sensitivity
Field selectable for 20%, 30%, 40%, 50%, 60%, or 70% beam obscuration.
Alarm Contacts
Normally Open (N/O) contacts rated 1 A, 60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive loads.
Trouble Contacts
Normally Closed (N/C) contacts rated 1 A, 60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive loads.
Auxiliary Alarm
Contacts:
Form "C" (N/O, C, N/C) contacts rated 1 A, 60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive loads.
Tamper
Receiver: Access door tamper switch in series with trouble contacts.
Transmitter: When the cover is removed, the cover tamper switch interrupts transmission.
System Signaling
Conventional four-wire system. Do not use with systems incorporating an alarm verification feature.
Signal Delay
Fire: Selectable 30 sec or 5 sec
Trouble: 20 ± 2 sec
Temperature
Storage and operating temperature range is -22°F to +130°F (-30°C to +54°C). For UL Listed
installations, the range is +32°F to +130°F (0°C to +54°C).
Mounting
The detectors are designed for mounting to 4-in. (10-cm) square or octagonal electrical boxes
(not supplied).
Listings
and Approvals
C-UL-US S3019
MSFM Permit #1943
NY City MEA Acceptance #MEA274-93-E
CSFM #7260-1062:106
FM Job #OX2A9.AY
CE
Standard
Accessories
D306 Remote Test Indicator Plate and Test Cable
Optional
Accessories
D307 Remote Test Indicator Plate
D308 Field Test Kit
D309 Alignment Light
D1005 Test Cord